Box Fill Calculator (NEC 314.16)

4 × #12 AWG conductors, one device yoke, internal clamps and one grounding conductor need 18.0 in³ — the smallest listed box that holds them is a 4" square x 1-1/4" at 18.0 in³.

Calculator

Conductors

Count each conductor that comes in and ends here, and each one that passes through. A conductor that begins and ends inside the box, such as a pigtail, is not counted; an unbroken conductor looped or coiled in the box, at least twice the length the code asks you to leave at a box, counts twice.

Each yoke counts twice. A device wider than one gang counts twice for every gang it needs.

The largest conductor connected to a yoke.

Up to four share one allowance; each one beyond four adds a quarter.

One allowance for each type present, at the largest conductor in the box.

All the clamps inside the box together count once. A connector that clamps outside the box does not.

Minimum Box Volume

18.0in³

Conductors
9.0 in³
Devices
4.5 in³
Clamps
2.25 in³
Grounds
2.25 in³
Fittings
0.0 in³

Suitable Boxes

4" square x 1-1/4" — 18.0 in³

3" x 2" x 3-1/2" device — 18.0 in³

FD 2-3/8" deep, single cover/gang — 18.0 in³

FS 1-3/4" deep, multiple cover/gang — 18.0 in³

4" square x 1-1/2" — 21.0 in³

Per NEC 2023 314.16(B), NEC 2023 Table 314.16(A), NEC 2023 Table 314.16(B)(1)

How it’s calculated

V = conductors + 2 × yokes + clamps + grounds + fittings, each in the volume for its conductor size

conductors
one volume for each conductor entering the box, at its own size: #14 AWG 2.0 in³, #12 AWG 2.25 in³, #10 AWG 2.5 in³, #8 AWG 3.0 in³, #6 AWG 5.0 in³
yokes
two volumes per yoke, at the largest conductor connected to that yoke
clamps
one volume for all internal clamps together, at the largest conductor in the box
grounds
one volume for up to four, at the largest of them, plus a quarter for each beyond four
fittings
one volume for each type of luminaire stud or hickey, at the largest conductor

The box then has to be at least that volume. The listed boxes come from the table of standard metal boxes; a box with its volume marked by the manufacturer is read from the marking instead.

A conductor that begins and ends inside the box is not counted, and wire connectors get no allowance.

Assumptions

  • Conductors 14 AWG through 6 AWG, the sizes this form counts. Where 4 AWG or larger conductors enter, the box also has to meet the separate rules for pull and junction boxes.
  • The box's own volume is the table's figure for a standard metal box, or the volume the manufacturer marked on it. Nonmetallic boxes, and metal boxes the table does not list, carry that marking.
  • A terminal block has no field of its own: it counts one allowance at the largest conductor terminated to it, so add it as one more conductor of that size.
  • Each yoke is counted at one conductor size: where two devices in a box are wired in different sizes, use the larger.
  • Isolated grounding conductors are counted with the other equipment grounding conductors; they get no allowance of their own.
  • Volumes are rounded to 0.01 in³ and the total to 0.1 in³.

Worked example

A junction box with two circuits and two receptacles

Six #12 AWG and three #10 AWG conductors, two device yokes wired in #12 AWG, internal clamps, and three grounding conductors of which the largest is #10 AWG.

  1. Conductors, each at the volume for its own size:6 × 2.25 + 3 × 2.5= 21.0 in³
  2. Two yokes, each twice the volume of the largest conductor connected to it:2 × 2 × 2.25= 9.0 in³
  3. All the internal clamps together, once, at the largest conductor in the box (#10 AWG):1 × 2.5= 2.5 in³
  4. Three grounding conductors — four or fewer share one allowance, at the largest of them:1 × 2.5= 2.5 in³
  5. Total21.0 + 9.0 + 2.5 + 2.5= 35.0 in³

Answer: 35.0 in³, so a 4-11/16" square x 2-1/8" at 42.0 in³ is the smallest listed box that takes it.

Open this example in the calculator

Code references

Section numbers are from NEC 2023 (NFPA 70). This page explains them in its own words and quotes no code text.

  • NEC 2023 314.16(B): what gets an allowance, and how much
  • NEC 2023 Table 314.16(B)(1): the volume required for one conductor of each size
  • NEC 2023 Table 314.16(A): the volume of each standard metal box

NEC 2026

Where the 2026 edition differs for this calculator:

  • 314.16(B): the list of things that get no volume allowance names splicing connectors as well, which is how they were already counted

Check which edition your AHJ enforces.

Read the NEC on NFPA’s free access page

Why answers online disagree

  • Counting a device once

    A yoke is two volumes, not one. A tool that counts a receptacle as a single conductor is one whole allowance short per device.

    Check: whether the other tool doubles the device.

  • Counting each ground

    Giving every grounding conductor its own allowance overstates a box with several cables in it. Four share one allowance, and the fifth onwards adds a quarter each.

    Check: how the other tool treats the second and later grounds.

  • Counting pigtails and wire nuts

    Neither is counted. A tool that counts every conductor end inside the box, rather than the conductors entering it, comes out high.

    Check: whether the other tool asks for conductors entering the box or wires in it.

  • The wrong conductor size for the extras

    Clamps, fittings and yokes are counted at the largest conductor they apply to, not at the smallest or at an average. In a box holding both 12 AWG and 10 AWG that is a quarter of a cubic inch each time.

    Check: which size the other tool used for the clamp and device allowances.

  • Box volume from a catalog

    A manufacturer's box is often larger than the table's standard figure, and its marked volume governs. A tool built on the table will sometimes call for a bigger box than the one in your hand needs.

    Check: the volume marked on the box itself.

Questions

What size box do I need for 4 #12 AWG conductors and a receptacle?

18.0 in³ with internal clamps and one grounding conductor, so a 4" square x 1-1/4" (18.0 in³) is the smallest box in the table that holds it. Two yokes in the same box would need 22.5 in³.

Does every grounding conductor count?

Not one each. Up to four grounding conductors share a single allowance, taken at the largest of them, and every one beyond four adds a quarter of that allowance. One ground here is 2.25 in³ and five is 2.81 in³.

Why does a switch or receptacle count twice?

A yoke or strap with a device on it is counted at twice the volume of the largest conductor connected to that yoke, because the device itself takes up room. A device too wide for one gang counts twice for each gang it needs to mount.

Do wire connectors and pigtails count?

No. Wire connectors get no allowance, and a conductor that both begins and ends inside the box — a pigtail or a jumper — is not counted at all. Only conductors that enter the box and either end there or pass through it are. An unbroken conductor left in a loop or coil at least twice the length the code asks you to leave at a box counts twice.

What about cable clamps?

All the clamps inside one box count once together, at the volume of the largest conductor in the box. A cable connector whose clamping mechanism sits outside the box gets no allowance.

Does this cover a big pull box?

Only the volume count, and only for conductors up to 6 AWG. Where 4 AWG or larger conductors enter a box, it also has to meet the separate rules for pull and junction boxes, which size it from the raceways entering it rather than from a count.

Related calculators

About this calculator

Written and maintained by Yusuf Can Samiloglu: MEP/HVAC design background, mechanical-engineering degree, not a licensed electrician.

How it’s checked: the calculation is the method of the Electric Master app, ported to the web and tested case by case against the app’s source code. Every table value was checked against the NEC 2023 values in at least two independent published sources.

Edition: NEC 2023. Your AHJ may enforce another edition or local amendments, and it has the final word. Read the NEC on NFPA’s free access page.

The App Store version of Electric Master (2.2.0) predates the NEC corrections this page follows; until its next update, its result can differ from this page for some inputs. Version 2.2.0 has an on/off switch for grounds and counts them as one allowance at 12 AWG whatever their number or size, counts every yoke at the largest conductor in the box, adds a deep-device allowance of its own and does not stop at two fitting types, so with more than four grounds, or a ground larger than 12 AWG, it asks for less room than this page.

Found a wrong number? Email [email protected].

Last updated:

Changelog
  • : The total volume is rounded up, so the figure shown is never below the true total.
  • : First version, NEC 2023. Conductors by size, device yokes counted by gang with their own conductor size, internal clamps, fitting types, and grounding conductors by count at the largest ground’s size; the boxes that hold the total come from Table 314.16(A).