Wire Ampacity Chart: Copper and Aluminum (NEC Table 310.16)

Under NEC 2023, 12 AWG copper carries 20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C (up to three current-carrying conductors, 30 °C ambient); for 50 A in the 75 °C column the smallest copper size is 8 AWG.

Calculator

Lookup Mode
Conductor Material
Temperature Rating

The column to read. Your terminals decide which one you may use (NEC 2023 110.14(C)(1)).

Ampacity — #12 AWG Copper

25A

60°C
20A
75°C
25A
90°C
30A
  • The large figure is the 75 °C column.
  • The overcurrent device for this size is limited to 20 A (240.4(D)).

Per NEC 2023 Table 310.16, NEC 2023 240.4(D)

Copper conductors: amperes by temperature rating (NEC 2023)

Amperes for copper conductors. Values from NEC 2023 Table 310.16 for up to three current-carrying conductors in a raceway, a cable or buried directly, at 30 °C (86 °F) ambient.
Size60 °C75 °C90 °C
14 AWG to 1 AWG
#14 AWGbreaker ≤ 15 A (240.4(D))152025
#12 AWGbreaker ≤ 20 A (240.4(D))202530
#10 AWGbreaker ≤ 30 A (240.4(D))303540
#8 AWG405055
#6 AWG556575
#4 AWG708595
#3 AWG85100115
#2 AWG95115130
#1 AWG110130145
1/0 AWG to 2000 kcmil
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475
700 kcmil385460520
750 kcmil400475535
800 kcmil410490555
900 kcmil435520585
1000 kcmil455545615
1250 kcmil495590665
1500 kcmil525625705
1750 kcmil545650735
2000 kcmil555665750

NEC 2023 also lists 18 AWG and 16 AWG copper, in the 90 °C column only (14 A and 18 A). The lookup and this chart start at 14 AWG, the smallest copper size for general wiring (NEC 2023 310.3(A)).

Before you use these values

  • The terminals decide the column: circuits of 100 A or less, and equipment marked for 14 AWG to 1 AWG conductors, use the 60 °C column unless the equipment is listed and marked for 75 °C; circuits over 100 A, and equipment marked for conductors larger than 1 AWG, use 75 °C (NEC 2023 110.14(C)(1)).
  • The 90 °C column is a starting point for correcting and adjusting a 90 °C conductor; the result may not exceed the column of the lowest-rated termination (NEC 2023 110.14(C)).
  • More than three current-carrying conductors together, or an ambient above 30 °C, lowers these values. Ampacity derating calculator
  • Services and main feeders of dwellings at 120/240 V, 100 A to 400 A, may be sized at 83 % of their rating under NEC 2023 310.12 instead; this chart does not apply it.
  • Single conductors in open air have their own, higher values (NEC 2023 310.17).
  • THHN is rated 90 °C in dry and damp locations, THWN 75 °C in dry and wet locations, and THWN-2 90 °C in dry and wet locations (NEC 2023 Table 310.4(1)).
  • Verify against the edition your AHJ enforces.

Aluminum conductors: amperes by temperature rating (NEC 2023)

Amperes for aluminum conductors. Values from NEC 2023 Table 310.16 for up to three current-carrying conductors in a raceway, a cable or buried directly, at 30 °C (86 °F) ambient.
Size60 °C75 °C90 °C
12 AWG to 1 AWG
#12 AWGbreaker ≤ 15 A (240.4(D))152025
#10 AWGbreaker ≤ 25 A (240.4(D))253035
#8 AWG354045
#6 AWG405055
#4 AWG556575
#3 AWG657585
#2 AWG7590100
#1 AWG85100115
1/0 AWG to 2000 kcmil
1/0 AWG100120135
2/0 AWG115135150
3/0 AWG130155175
4/0 AWG150180205
250 kcmil170205230
300 kcmil195230260
350 kcmil210250280
400 kcmil225270305
500 kcmil260310350
600 kcmil285340385
700 kcmil315375425
750 kcmil320385435
800 kcmil330395445
900 kcmil355425480
1000 kcmil375445500
1250 kcmil405485545
1500 kcmil435520585
1750 kcmil455545615
2000 kcmil470560630

Before you use these values

  • The aluminum columns also cover copper-clad aluminum (NEC 2023 Table 310.16).
  • The terminals decide the column: circuits of 100 A or less, and equipment marked for 14 AWG to 1 AWG conductors, use the 60 °C column unless the equipment is listed and marked for 75 °C; circuits over 100 A, and equipment marked for conductors larger than 1 AWG, use 75 °C (NEC 2023 110.14(C)(1)).
  • The 90 °C column is a starting point for correcting and adjusting a 90 °C conductor; the result may not exceed the column of the lowest-rated termination (NEC 2023 110.14(C)).
  • More than three current-carrying conductors together, or an ambient above 30 °C, lowers these values. Ampacity derating calculator
  • Services and main feeders of dwellings at 120/240 V, 100 A to 400 A, may be sized at 83 % of their rating under NEC 2023 310.12 instead; this chart does not apply it.
  • Single conductors in open air have their own, higher values (NEC 2023 310.17).
  • THHN is rated 90 °C in dry and damp locations, THWN 75 °C in dry and wet locations, and THWN-2 90 °C in dry and wet locations (NEC 2023 Table 310.4(1)).
  • Verify against the edition your AHJ enforces.

Smallest conductor for common circuit ratings

The smallest size whose NEC 2023 Table 310.16 value reaches each standard rating (NEC 2023 240.6(A)), by metal and column, with up to three current-carrying conductors, 30 °C ambient. A table lookup, not a wire-size answer: read the notes below the table first.
AmperesCopper 60 °CCopper 75 °CAluminum 60 °CAluminum 75 °CCalculator
15 A#14 AWG#14 AWG#12 AWG#12 AWGSize it for a 15 A circuit
20 A#12 AWG#14 AWGlimited to 15 A by 240.4(D)#10 AWG#12 AWGlimited to 15 A by 240.4(D)Size it for a 20 A circuit
25 A#10 AWG#12 AWGlimited to 20 A by 240.4(D)#10 AWG#10 AWGSize it for a 25 A circuit
30 A#10 AWG#10 AWG#8 AWG#10 AWGlimited to 25 A by 240.4(D)Size it for a 30 A circuit
35 A#8 AWG#10 AWGlimited to 30 A by 240.4(D)#8 AWG#8 AWGSize it for a 35 A circuit
40 A#8 AWG#8 AWG#6 AWG#8 AWGSize it for a 40 A circuit
45 A#6 AWG#8 AWG#4 AWG#6 AWGSize it for a 45 A circuit
50 A#6 AWG#8 AWG#4 AWG#6 AWGSize it for a 50 A circuit
60 A#4 AWG#6 AWG#3 AWG#4 AWGSize it for a 60 A circuit
70 A#4 AWG#4 AWG#2 AWG#3 AWGSize it for a 70 A circuit
80 A#3 AWG#4 AWG#1 AWG#2 AWGSize it for a 80 A circuit
90 A#2 AWG#3 AWG1/0 AWG#2 AWGSize it for a 90 A circuit
100 A#1 AWG#3 AWG1/0 AWG#1 AWGSize it for a 100 A circuit
110 A#1 AWG#2 AWG2/0 AWG1/0 AWGSize it for a 110 A circuit
125 A1/0 AWG#1 AWG3/0 AWG2/0 AWGSize it for a 125 A circuit
150 A3/0 AWG1/0 AWG4/0 AWG3/0 AWGSize it for a 150 A circuit
175 A4/0 AWG2/0 AWG300 kcmil4/0 AWGSize it for a 175 A circuit
200 A250 kcmil3/0 AWG350 kcmil250 kcmilSize it for a 200 A circuit
225 A300 kcmil4/0 AWG400 kcmil300 kcmilSize it for a 225 A circuit
250 A350 kcmil250 kcmil500 kcmil350 kcmilSize it for a 250 A circuit
300 A500 kcmil350 kcmil700 kcmil500 kcmilSize it for a 300 A circuit
350 A600 kcmil500 kcmil900 kcmil700 kcmilSize it for a 350 A circuit
400 A750 kcmil600 kcmil1250 kcmil900 kcmilSize it for a 400 A circuit

Before you use these values

  • The terminals decide the column: circuits of 100 A or less, and equipment marked for 14 AWG to 1 AWG conductors, use the 60 °C column unless the equipment is listed and marked for 75 °C; circuits over 100 A, and equipment marked for conductors larger than 1 AWG, use 75 °C (NEC 2023 110.14(C)(1)).
  • A continuous load needs conductors and an overcurrent device for 125 % of it (NEC 2023 210.19(A)(1) and NEC 2023 210.20(A)); look up that current instead.
  • A marked cell is a small conductor that NEC 2023 240.4(D) does not allow behind a device of that rating; the wire size calculator moves on to the first size it allows.
  • More than three current-carrying conductors together, or an ambient above 30 °C, can call for a larger size. Ampacity derating calculator
  • A long run can need a larger size to keep the voltage drop down. Voltage drop calculator
  • Services and main feeders of dwellings at 120/240 V, 100 A to 400 A, may be sized at 83 % of their rating under NEC 2023 310.12 instead; this table does not apply it.

How it’s calculated

By wire size: Itable = the Table 310.16 value for the size, the metal and the column

By amps: the first 5 sizes, from 14 AWG up, with Itable ≥ Irequired

Itable
the table ampacity in amperes, for up to three current-carrying conductors, 30 °C ambient
Irequired
the current you enter under Required Ampacity

Copper starts at 14 AWG and aluminum at 12 AWG, the smallest sizes NEC 2023 310.3(A) allows for general wiring; the table gives aluminum no value below that.

The first size in the list is marked “Smallest”. The lookup applies no terminal rating, no 125 % for continuous loads, no 240.4(D) limit and no derating; the wire size calculator applies all four.

Assumptions

  • Every value is for up to three current-carrying conductors in a raceway, a cable or the earth, at 30 °C (86 °F) ambient. More conductors or a hotter ambient lower it.
  • Conductors rated up to 2000 V, the range the table covers.
  • Copper or aluminum. Copper-clad aluminum reads the aluminum columns.
  • The lookup reads the table only: terminals, continuous loads, 240.4(D) and derating are left to you or to the wire size calculator.
  • Sizes from 14 AWG to 2000 kcmil; the smaller copper rows of the table are only mentioned under the copper chart.
  • Whole amperes, as the table lists them.
  • Single conductors in open air (NEC 2023 310.17), dwelling services sized under NEC 2023 310.12 and manufacturer ratings are not covered.

Worked example

A 100 A circuit, looked up by amps

Which copper and aluminum sizes does the table give for 100 A? The column depends on the terminals: for a 100 A circuit, NEC 2023 110.14(C)(1) points to 60 °C unless the equipment is listed and marked for 75 °C. Both are shown.

  1. Copper, 75 °C column: the first size with at least 100 A4 AWG has 85 A; 3 AWG has 100 A= 3 AWG copper
  2. Aluminum, 75 °C column: the first size with at least 100 A2 AWG has 90 A; 1 AWG has 100 A= 1 AWG aluminum
  3. Copper, 60 °C column: the first size with at least 100 A2 AWG has 95 A; 1 AWG has 110 A= 1 AWG copper
  4. Aluminum, 60 °C column: the first size with at least 100 A1 AWG has 85 A; 1/0 AWG has 100 A= 1/0 AWG aluminum

Answer: With terminals listed and marked for 75 °C: 3 AWG copper or 1 AWG aluminum. Otherwise the 60 °C column applies: 1 AWG copper or 1/0 AWG aluminum. A continuous load or derating can push the size up; the wire size calculator checks both.

Open this example in the lookup

Code references

Section numbers are from NEC 2023 (NFPA 70). This page explains them in its own words and quotes no code text.

  • NEC 2023 Table 310.16: ampacities by size, metal and temperature column, for up to three current-carrying conductors, 30 °C ambient
  • NEC 2023 110.14(C)(1): which column the terminals allow when the equipment is not marked for a higher one
  • NEC 2023 110.14(C): the column is limited by the lowest-rated termination; a higher-rated conductor may start from its own column for correction and adjustment
  • NEC 2023 240.4(D): the largest overcurrent device for small copper and aluminum conductors
  • NEC 2023 240.6(A): the standard overcurrent-device ratings, the rows of the reverse table
  • NEC 2023 310.3(A): the smallest copper and aluminum sizes for general wiring
  • NEC 2023 210.19(A)(1): branch-circuit conductors: the noncontinuous load plus 125 % of the continuous load
  • NEC 2023 215.2(A)(1): feeder conductors: the same 125 % rule
  • NEC 2023 210.20(A): the overcurrent device: the same 125 % rule
  • NEC 2023 Article 100: a continuous load is one whose maximum current is expected to last 3 hours or more
  • NEC 2023 Table 310.15(B)(1)(1): correction factors for an ambient other than 30 °C
  • NEC 2023 Table 310.15(C)(1): how much the ampacity drops when one raceway or cable holds more than three current-carrying conductors
  • NEC 2023 310.12: dwelling services and main feeders (120/240 V, 100 A to 400 A) sized at 83 % of their rating (not applied here)
  • NEC 2023 310.17: single conductors in open air, with higher values than Table 310.16
  • NEC 2023 Table 310.4(1): insulation temperature ratings, e.g. THHN, THWN and THWN-2
  • NEC 2023 334.80: NM cable uses the 60 °C ampacity; the 90 °C value may be the starting point for derating

NEC 2026

Where the 2026 edition differs for this calculator:

  • Table 310.16: the 18 AWG row is gone; 16 AWG copper is rated 10 A at 60 °C, and its higher-temperature values serve adjustment and correction only; a 14 AWG copper-clad aluminum row is added; the other values are unchanged. This page follows NEC 2023.

Check which edition your AHJ enforces.

Read the NEC on NFPA’s free access page

Why answers online disagree

  • A different column

    A chart that prints one number per size has picked a column for you, often 75 °C or 90 °C. 12 AWG copper is 20 A, 25 A and 30 A depending on the column, and the terminals decide which one counts.

    Check: which temperature column the other chart used.

  • An older code book

    Several cells differ from older editions, among them 6 AWG aluminum at 90 °C (55 A here), 600 kcmil copper at 60 °C (350 A here), 800 kcmil aluminum at 90 °C (445 A here) and 2000 kcmil copper at 60 °C (555 A here). A chart copied from an older book can show another value there or elsewhere.

    Check: which edition the chart follows.

  • Another table

    NEC 2023 310.17 gives higher values for single conductors in open air, NEC 2023 310.12 sizes some dwelling services and main feeders at 83 % of their rating, and manufacturers publish tables for their own cables and conditions.

    Check: which table and which conditions the chart is based on.

  • Chassis-wiring charts

    Charts for chassis or point-to-point wiring in electronics list much higher currents for the same gauge, for short wires in open air. They do not apply to building wiring.

    Check: that the chart is meant for building wiring under the NEC.

  • NM cable

    NM cable is held to the 60 °C ampacity; the 90 °C value only serves as the starting point for derating (NEC 2023 334.80). A chart listing 12 AWG NM at 30 A reads the wrong column.

    Check: the wiring method.

  • Copper-clad aluminum

    Copper-clad aluminum reads the aluminum columns. A chart that groups it with copper overstates it.

    Check: the conductor metal.

  • Ampacity is not the breaker size

    NEC 2023 240.4(D) caps the overcurrent device for small conductors whatever their ampacity: copper 14 AWG 15 A, 12 AWG 20 A and 10 AWG 30 A; aluminum 12 AWG 15 A and 10 AWG 25 A. 12 AWG copper has 30 A in the 90 °C column but still takes a device of 20 A at most — except where NEC 2023 240.4(E) or NEC 2023 240.4(G) sends the circuit elsewhere, as motor and air-conditioning circuits go to Articles 430 and 440.

    Check: 240.4(D) before picking a breaker.

Questions

What is the ampacity of 12 AWG copper wire?

20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C under NEC 2023 Table 310.16, with up to three current-carrying conductors, 30 °C ambient. Whatever the column, NEC 2023 240.4(D) limits the overcurrent device ahead of it to 20 A.

What is the ampacity of 4/0 AWG copper and aluminum?

4/0 AWG copper: 195 A at 60 °C, 230 A at 75 °C and 260 A at 90 °C. 4/0 AWG aluminum: 150 A at 60 °C, 180 A at 75 °C and 205 A at 90 °C. These are the NEC 2023 Table 310.16 values with up to three current-carrying conductors, 30 °C ambient; the terminals decide which column you may use.

What size copper wire carries 50 A?

By the table alone: 6 AWG in the 60 °C column (55 A), 8 AWG in the 75 °C column (50 A) and 8 AWG in the 90 °C column (55 A). A 50 A circuit reads the 60 °C column unless its terminals are listed and marked for 75 °C, and the 90 °C value only serves as a starting point for derating. A continuous 50 A load needs 125 % of it, 62.5 A, which moves the 60 °C copper size from 6 AWG to 4 AWG.

Which temperature column should I use?

The lowest temperature rating among the conductor’s insulation and everything it connects to (NEC 2023 110.14(C)). Under NEC 2023 110.14(C)(1), circuits of 100 A or less, and equipment marked for 14 AWG to 1 AWG conductors, use the 60 °C column unless the equipment is listed and marked for 75 °C; circuits over 100 A, and equipment marked for conductors larger than 1 AWG, use 75 °C. The 90 °C column is where a 90 °C conductor starts before correction and adjustment; the result still may not exceed the terminals’ column.

Related calculators

About this calculator

Written and maintained by Yusuf Can Samiloglu: MEP/HVAC design background, mechanical-engineering degree, not a licensed electrician.

How it’s checked: the calculation is the method of the Electric Master app, ported to the web and tested case by case against the app’s source code. Every table value was checked against the NEC 2023 values in at least two independent published sources.

Edition: NEC 2023. Your AHJ may enforce another edition or local amendments, and it has the final word. Read the NEC on NFPA’s free access page.

The App Store version of Electric Master (2.2.0) predates the NEC corrections this page follows; until its next update, its result can differ from this page for some inputs. Version 2.2.0 carries older values in a few cells — 6 AWG aluminum at 90 °C, 600 kcmil copper at 60 °C, 800 kcmil aluminum at 90 °C and 2000 kcmil copper at 60 °C among them — and its by-amps list can offer a size the table rates for adjustment only.

Found a wrong number? Email [email protected].

Last updated:

Changelog
  • : First version, NEC 2023 values for copper from 14 AWG and aluminum from 12 AWG to 2000 kcmil, with a lookup by size and by amps.